2.Single phasing & protection

September 26, 2018 Posted by AK No comments

When one of the 3 line supplying current to a 3 phase induction motor becomes open circuited single phasing occurs. If motor is already running it will continue to run. The excess

current will passes through remaining 2 wires and over heating will occur. If motor is in stopped position it will not start due to open circuit fault in one line.

    
In delta connected motor if supply line L1 is open circuited then phase C will carry more than 3 times normal current under full load conditions. While phase A & B are in series carry more than full load current.

In star connected motor if supply line L1 is open circuited then current flowing at full load in lines L2 & L3 will be in the order of 250% of normal full load current.

The protection given against single phasing is a combined overload and single phasing relay. This include 3 overload relay with trip contact so arranged that it will trip if displacement of one overload element differs from other.