1.Visual inspection of all parts
2.Turnoff the positive pressure mechanism and and open the main valve and check the pressure in the bottle (must be 80% full)
3.Keep the line pressure for 1 minutes.It should not drop 10 bar in 1 minutes.
4.Slowly release the pressure. alarm should sound at 55 bar.