(i) Core losses or Iron losses
Eddy current loss and hysteresis loss depend upon the magnetic
properties of the material used for the construction of core. Hence
these losses are also known as core losses or iron losses.
- Hysteresis loss in transformer: Hysteresis loss is due to reversal of magnetization in the transformer core. This loss depends upon the volume and grade of the iron, frequency of magnetic reversals and value of flux density.
- Eddy current loss in transformer: In transformer, AC current is supplied to the primary winding which sets up alternating magnetizing flux. When this flux links with secondary winding, it produces induced emf in it. But some part of this flux also gets linked with other conducting parts like steel core or iron body or the transformer, which will result in induced emf in those parts, causing small circulating current in them. This current is called as eddy current. Due to these eddy currents, some energy will be dissipated in the form of heat.
(ii) Copper loss in transformer
Copper loss is due to ohmic resistance of the transformer windings. Copper loss for the primary winding is I12R1 and for secondary winding is I22R2. Where, I1 and I2 are current in primary and secondary winding respectively, R1 and R2
are the resistances of primary and secondary winding respectively. It
is clear that Cu loss is proportional to square of the current, and
current depends on the load. Hence copper loss in transformer varies
with the load
Two transformer tests are performed to find the parameters of equivalent circuit of transformer and losses of the transformer. Open circuit test and short circuit test on transformer.
Open circuit or No load test on Transformer
Open circuit test or no load test on a transformer is performed to determine 'no load loss (core loss)' and 'no load current.
Usually high voltage (HV) winding is kept open and the low voltage (LV)
winding is connected to its normal supply. A wattmeter (W), ammeter (A)
and voltmeter (V) are connected to the LV winding as shown in the
figure. Now, applied voltage is slowly increased from zero to normal
rated value of the LV side with the help of a variac. When the applied
voltage reaches to the rated value of the LV winding, readings from all
the three instruments are taken.
The ammeter reading gives the no load current I0. As I0 itself is very small, the voltage drops due to this current can be neglected.
The input power is indicated by the wattmeter (W). And as the other side
of transformer is open circuited, there is no output power. Hence, this
input power only consists of core losses and copper losses. As
described above, no-load current is so small that these copper losses
can be neglected. Hence, now the input power is almost equal to the core
losses. Thus, the wattmeter reading gives the core losses of the
transformer.Short circuit or Impedance test on Transformer
The LV side of transformer is short circuited and wattmeter (W), voltmere (V) and ammeter (A) are connected on the HV side of the transformer. Voltage is applied to the HV side and increased from the zero until the ammeter reading equals the rated current. All the readings are taken at this rated current.The ammeter reading gives primary equivalent of full load current (Isc).
The voltage applied for full load current is very small as compared to rated voltage. Hence, core loss due to small applied voltage can be neglected. Thus, the wattmeter reading can be taken as copper loss in the transformer.