A total load of 8000 KW at 0.8 power factor is supplied by two alternators in parallel. One alternator supplies 6000KW at 0.9 power factor. Find the KVA rating of the other alternator and the power factor.
If you are noticing some error in problems kindly comment below.Thanks
If you are noticing some error in problems kindly comment below.Thanks
Given
Total power PT = 8000 KW
Total pf Cos øT = 0.8
Generator 1 power P1 = 6000 KW
Generator 1 pf Cos ø1 = 0.9
To find
1. Generator 2 apparent power, KVA2
2. Generator 2 pf, Cos ø2
Apparent power total, KVAT = KWT / Cos øT
= 8000 / 0.8
= 10000 KVA
Reactive power total, KVArT = Sin øT X KVAT
= 0.6 X 10000
= 6000 KVArT
Apparent power Generator 1, KVA1 = KW1 / Cos ø1
= 6000 / 0.9
= 6667 KVA
Reactive power Generator 1, KVAr1 = Sin ø1 X KVA1
= 0.4357 X 6667
= 2905 KVAr
Power of generator 2, KW2 = KWT – KW1
= 8000 - 6000
= 2000 K
Reactive power of generator 2, KVAr2 = KVArT – KVAr1
Reactive power of generator 2, KVAr2 = KVArT – KVAr1
= 6000 - 2905
= 3095 KVAr
1. Apparent power of generator 2, KVA22 = KW22 + KVAr22
√ KVAr2 = √ (KW22 + KVAr22 )
= √ (20002 + 30952)
= 3684 KVA
2. Power factor of generator 2, Cosø2 = KW2 / KVA2
= 2000 / 3684
= 0.543