Two 10 MVA 3 phase alternators operate in parallel to supply at 0.8 power factor with lagging load of 15 MVA. If output of one alternator is 8 MVA at 0.9 lagging.
1) Calculate the output of second alternator2) Calculate the value of power factor of second alternator
If you are noticing some error in problems kindly comment below.Thanks
Given
MVAtotal = 15 MVA
Φtotal = 0.8 ; sin Φtotal = 0.6
For Alternator 1
MVA1 = 8 MVA
Φ1 = 0.9 ; SinΦ1 = 0.436
To find
1. MVA2
2. Φ2
Solution
Total load MWtotal = MVAtotal x cos Φtotal
= 15 x 0.8
= 12 MW
Total Reactive load MVARtotal = MVAtotal x sin Φtotal
= 15 x 0.6
= 9 MVA
Alternator 1 load MW1 = MVA1 x cos Φ1
= 8 x 0.9
= 7.2 MW
Alternator 1 Reactive load MVAR1 = MVA1 x sin Φ1
= 8 x 0.436
= 3.49 MVAR
For Alternator 2 Load MW2 = MWtotal - MW1
= 12 - 7.2
= 4.8 MW
Alternator 2 Reactive load MVAR2 = MVARtotal - MVAR1
= 9 - 3.49
= 5.51 MVAR
1. MVA22 = MW22 + MVAR22
MVA2 = Square root of (MW2 + MVAR2)
= Square root of (4.82 + 5.512)
MVA2 = 7.3 MVA
2. Cos Φ2 = MW2 / MVA2
= 4.8 / 7.3
Cos Φ2 = 0.66 (lag)