24.Two generators are running in parallel, KW is same but current is different why

September 26, 2018 Posted by AK No comments
This phenomenon is due to the improper reactive load sharing. This kind of situation, the individual output voltages of the alternators will be different. While running single, this voltage difference will not be a problem. But while running in parallel, they will not share the reactive load equally. For to make the reactive load sharing equally, we will have to adjust slightly one generator’s output voltage while they are running parallel until we see the current also sharing equally.